November 05, 2026

Your own equipment triggers Código de Red fines

Mexico’s Código de Red holds every high-voltage connected facility and every medium-voltage facility with contracted demand of 1 MW or more to a power factor between 0.97 lagging and 1.0, at least 95% of the time in each monthly period, measured in five-minute intervals. That band replaced the 0.95 floor that applied for the code’s first ten years. The Comisión Nacional de Energía, a technical body sectorized to the Secretaría de Energía, now enforces it in place of the dissolved Comisión Reguladora de Energía: it orders verification visits and imposes most sanctions, while SENER itself sanctions grave quality and reliability violations of its own dispositions under the Ley del Sector Eléctrico. Given the size of their electrical load, that threshold captures nearly every steel mill, mine, and chemical plant operating in the country.

Most compliance guidance treats that as the whole story: a threshold, a regulator, a fine schedule to avoid. It understates the exposure for this sector specifically. Héctor Villaseñor Lomelí, ABB’s market manager for high voltage and power grids, told Energía Hoy in a July 22, 2019 interview that foundry processes, grinding operations, extraction, and conveyor belts generate significant distortion. He named steel and mining explicitly as the industries producing the most electrical grid disturbance in the country. Sectors like food and beverage or automotive face more compliance surprise and cause less of the underlying problem. The same reporting cited a siderurgic facility in Lázaro Cárdenas where foundry-related disturbances damaged other users’ electrical equipment.

That distinction matters for how a plant manager should read the 0.97 threshold, in force since April 9, 2026 under the Código de Red 2.0 (CRE resolution RES/550/2021, DOF December 31, 2021). A precision machining shop worried about Código de Red compliance is managing exposure to a problem largely caused elsewhere on the grid. A steel mill running an electric arc furnace, a mine running crushers and haul conveyors, or a chemical plant running electrolytic cells is managing exposure to a problem its own process creates. The fine schedule in force since the Ley del Sector Eléctrico took effect in March 2025 scales with how long that signature goes uncorrected, not with whether the plant considers itself a compliance-focused operation.

The penalties now in force

The penalty structure now sits in article 184 of the Ley del Sector Eléctrico, published in the DOF on March 18, 2025, which replaced article 165 of the Ley de la Industria Eléctrica and raised every UMA band. It runs on a tiered basis keyed to the severity and nature of the violation. Grave violations, including ignoring CENACE dispatch instructions, grave breaches of quality, reliability, continuity, or security standards as judged by SENER, and operating without a permit or registration, carry a fine of 10% of the company’s gross revenue from the prior year, a flat rate where the old law set a 2% to 10% range. Withholding required information, non-grave breaches of the quality, reliability, continuity, and security rules, unauthorized energy sales, and obstructing authorized inspectors carry fines of 128,000 to 514,000 times the daily value of the Unidad de Medida y Actualización, the UMA, up from 50,000 to 200,000. Meter tampering and failing to give inspectors the facilities they require carry a separate band of 26,000 to 128,000 UMA, up from 10,000 to 50,000. Shortfalls in contracted capacity, coverage, or CELs run 6 to 50 UMA per megawatt, megawatt-hour, or certificate. The CNE can fine unauthorized grid connections and consumption outside a contract at up to three times the value of the energy involved. The law doubles the penalty for repeat violations and triples it, with service suspension, for contumacious ones.

INEGI set the 2026 daily UMA value at 117.31 pesos, effective February 1, 2026, per its January 2026 press release. That converts the UMA-denominated bands into real numbers a finance committee can use. The 128,000 to 514,000 UMA tier for a quality breach, information withholding, or obstructing an inspector runs from roughly 15.0 million to 60.3 million pesos. That is approximately 799,000 to 3.21 million dollars at the Banxico FIX of 18.7962 pesos per dollar on October 30, 2026. The meter-tampering band runs from roughly 3.05 million to 15.0 million pesos. For illustration only, and not as a reported figure, a grave violation at a plant with 2 billion pesos in annual revenue would draw a fine of 200 million pesos under the 10% provision. None of these are hypothetical maximums reserved for the worst operators in the country. They are the standard schedule that now applies to any high-voltage or large medium-voltage facility the CNE or SENER inspects and finds out of compliance.

Why your own equipment triggers the fine

The mechanism connecting heavy industrial process to grid disturbance is straightforward. An electric arc furnace draws current in erratic, high-magnitude pulses as it strikes and sustains an arc through scrap steel, producing both harmonic distortion and voltage flicker as a normal byproduct of melting, not a malfunction. Large mining equipment, crushers, grinding mills, and conveyor drives run on variable-frequency drives and large induction motors that behave the same way electrically, as non-linear loads that inject harmonic current back into the grid. Chemical plants running electrolytic processes carry a similar profile. None of this is a defect specific to any one operator. It is the electrical signature of the processes that define these three industries.

Harmonic distortion limits under Código de Red reference CFE’s technical specification L0000-45 and IEEE Standard 519, and both work off a ratio. It compares the short-circuit current available at a facility’s point of connection with its own 12-month average maximum load current, per a December 20, 2019 technical explainer published by Radthink. That ratio, not a flat percentage, is what a plant is actually held to. A heavy industrial load connected to a comparatively weak point on the grid has less room to absorb its own distortion before crossing the compliance threshold. A stronger node gives more room. Weak connection points are common for mining operations in remote locations, and for steel and chemical plants sited away from the densest parts of the transmission network. The same equipment can be compliant in one location and non-compliant in another, purely as a function of grid strength at the point of connection.

What the penalty costs you

The direct fine exposure calculated above is the number a finance committee sees first. It is not the biggest number. A facility whose power factor sits below the new 0.97 threshold pays a demand-charge penalty on every bill until it corrects the deficiency. That cost compounds monthly. A fine lands once. Harmonic distortion also damages a facility’s own transformers and trips its own protection systems, a documented consequence of uncorrected harmonic loading according to the same Código de Red 2.0 guidance cited above. Repair costs and unplanned downtime land on top of any regulatory penalty. CENACE can also identify a facility as a disturbance source affecting other users on the same node, the exact scenario documented at the Lázaro Cárdenas siderurgic facility. That reputational and relationship exposure with the grid operator outlasts a single fine cycle.

A plant that has never measured its own power factor against the 0.97 band is very likely paying a demand-charge penalty on every invoice already, and one billing month of interval data settles whether that is you. Talk to an advisor.

The capital case for correction is more favorable than the fine schedule alone suggests, because the same equipment addresses both problems at once. Harmonic filters and power factor correction capacitor banks reduce the demand-charge penalty a plant pays every month, independent of whether the CNE or SENER ever inspects the facility. The same hardware moves the plant toward the compliance threshold. That dual return, corrected monthly billing plus reduced regulatory exposure, is the argument that turns this from a defensive compliance spend into a capital project with its own payback logic. Immediate deduction rates for new fixed assets under the Plan México decree, published in the DOF on January 21, 2025, run from 41% to 91% for assets acquired in 2025 and 2026 and from 35% to 89% from 2027 through September 30, 2030, set by the taxpayer’s activity: 60% then 54% for primary metal production, 76% then 71% for mining, 70% then 65% for chemicals. Acting before the rates step down on January 1, 2027 shortens that payback further.

The wider market context

The regulatory tightening lands on a grid that is already running closer to its limits than the transmission network serving it can comfortably support. National electricity demand grew 3.4% and 3.5% in 2022 and 2023 while transmission infrastructure expanded by only 0.09% and 0.10% in those same years, according to the Mexican Institute for Competitiveness. A grid running that close to capacity has less tolerance for harmonic loading and voltage disturbance from any single large industrial connection. That is part of why the CNE and SENER have reason to focus enforcement on heavy-load sectors. Steel producers face an additional pressure from a different direction. DeAcero signed a 20-year power purchase agreement in March 2017 with IEnova for the full output of the 110 MW Pima Solar plant in Caborca, Sonora, a 115 million dollar project supplying energy, capacity, and CELs that DeAcero said would move roughly 20% of its energy consumption to renewable supply. A major domestic steel producer restructured its power supply years before the 0.97 band arrived, for reasons that run alongside its grid compliance obligations and not instead of them. The European Union’s Carbon Border Adjustment Mechanism moved into its definitive economic phase on January 1, 2026, and iron and steel are among the product categories it explicitly covers. Importers buy their first CBAM certificates from February 1, 2027 and surrender them for 2026 imports by September 30, 2027. A steel exporter’s power decisions are now priced from two directions at once, domestic grid compliance and export-market carbon accounting. The two run on separate regulatory tracks.

The case against acting now

Enforcement of Código de Red has a mixed track record. According to Forbes México, the CRE had not deployed inspectors or verification units by January 2020. That was nearly four years after the code first took effect in April 2016 and nine months after the April 2019 compliance deadline the original code set. Whether the shift to CNE oversight since March 2025 produces meaningfully more inspections than the prior regime did is a fair question. It may mostly change which agency’s letterhead appears on the notice. A plant that has operated for years without a documented violation despite an uncorrected power factor or harmonic profile has some basis for skepticism that enforcement risk alone should force an urgent capital decision.

That skepticism has a limit. The fine schedule itself does not require a plant to be caught by a roving inspector. Routine interconnection reviews can find a violation. So can a dispute investigation triggered by a neighboring user’s complaint, the kind of disturbance documented at Lázaro Cárdenas. So can CENACE’s monitoring of node-level power quality. All of them trigger the same penalty structure. A plant can correct its power factor and harmonic profile now, or wait for stronger evidence of active enforcement. In the interim it pays the recurring demand-charge penalty every month, whether or not the CNE ever sends an inspector. The monthly cost accrues either way.

What to fix before the next bill

Commission a Class A power quality audit at the bus feeding your highest-distortion equipment first. That means your electric arc furnace, your largest crusher or conveyor drive, or your electrolytic cell line. Do not audit the whole plant uniformly. This identifies both your current power factor against the 0.97 threshold and your harmonic distortion relative to the short-circuit current ratio that actually governs your compliance obligation.

Translate your specific exposure into pesos using your own prior-year revenue and contracted capacity against the fine bands above. The illustrative figures here are not your number. A plant that has never modeled this number cannot weigh a correction project against its actual downside, only against a general sense that penalties exist.

Prioritize correction equipment, harmonic filters and power factor capacitor banks, at the load points your own process identifies as the source, not a single plant-wide fix. The demand-charge savings from correcting your worst offender alone frequently justify the investment before any fine exposure is counted.

Time the capital request against the accelerated depreciation window that runs through 2030. A correction project that also reduces your monthly demand charge and your harmonic-related equipment wear has three separate return streams. Build the board case around all three, not the compliance deadline alone. That is the stronger argument for board approval this cycle.

Power Quality and Grid Code Risk Review

We take Class A measurements at the bus feeding your highest-distortion equipment, test your harmonics against the short-circuit ratio that governs your obligation, and price the Ley del Sector Eléctrico fine bands against your own prior-year revenue. Send a single-line diagram and the measurement window is days on site.

Talk to a Mexico Energy Partners advisor or email info@mexicoenergypartners.com. Mexico Energy Partners sells no equipment and is compensated only by the client.

Sources

  • Comisión Reguladora de Energía, resolution RES/550/2021, Código de Red 2.0, DOF December 31, 2021, Manual Regulatorio de Requerimientos Técnicos para la Conexión de Centros de Carga: power factor 0.95 to 1.0 through April 8, 2026 and 0.97 lagging to 1.0 thereafter, five-minute measurement under NOM-001-CRE/SCFI-2019, at least 95% of the time per monthly period, for all high-voltage load centers and medium-voltage load centers with contracted demand of 1 MW or more. Original Código de Red: RES/151/2016, DOF April 8, 2016.
  • Ley del Sector Eléctrico, DOF March 18, 2025, in force March 19, 2025: article 11 (CNE verification and sanction powers), article 184 (fine tiers: 10% of prior-year gross revenue; 128,000 to 514,000 UMA; 26,000 to 128,000 UMA; 6 to 50 UMA per MW, MWh or CEL; up to three times the value of energy consumed; double for repeat and triple for contumacious violations) and article 185 (SENER imposes the grave quality and reliability sanction when the breached dispositions are its own, otherwise the CNE does). Ley de la Comisión Nacional de Energía, DOF March 18, 2025, article 2.
  • ABB market manager Héctor Villaseñor Lomelí’s assessment that foundry processes, grinding operations, extraction, and conveyor belts generate significant grid distortion, identification of steel and mining as leading disturbance sources, and the Lázaro Cárdenas siderurgic facility case. Energía Hoy, “Cómo afecta el Código de Red por sector, puntos clave para corregir el sistema,” July 22, 2019.
  • Harmonic distortion limits under Código de Red referencing CFE technical specification L0000-45 and IEEE Standard 519, calculated relative to the ratio between short-circuit current and 12-month average maximum load current. Radthink, “Código de Red: calidad de la potencia, parte 1, distorsión armónica,” December 20, 2019.
  • 2026 daily UMA value of 117.31 pesos, effective February 1, 2026. INEGI, Comunicado de Prensa 1/26, “Unidad de Medida y Actualización (UMA),” January 8, 2026.
  • Banco de México, FIX exchange rate of 18.7962 pesos per US dollar, October 30, 2026.
  • National electricity demand growth of 3.4% (2022) and 3.5% (2023) versus transmission network expansion of 0.09% and 0.10% in the same years. IMCO, “Sin transmisión eléctrica no será posible acelerar la transición energética” and “México ante la saturación de las redes eléctricas,” September 19, 2024.
  • IEnova and DeAcero, 20-year contract for the 110 MW Pima Solar plant in Caborca, Sonora, 115 million dollar investment, energy, capacity and CELs, roughly 20% of DeAcero’s consumption from renewables. El Financiero, “IEnova firma contrato de 115 mdd para proveer energía a Deacero,” March 27, 2017; PV Tech, March 28, 2017.
  • Decreto por el que se otorgan estímulos fiscales para apoyar la estrategia nacional denominada Plan México, DOF January 21, 2025, artículo segundo: immediate deduction of 41% to 91% (2025 and 2026) and 35% to 89% (2027 to September 30, 2030) by activity.
  • European Commission, CBAM definitive regime from January 1, 2026, covering cement, iron and steel, aluminium, fertilisers, electricity and hydrogen; Regulation (EU) 2025/2083 of October 8, 2025 (Official Journal October 17, 2025): certificate sales from February 1, 2027, first surrender by September 30, 2027.
  • CRE’s lack of deployed inspectors and verification units after the Código de Red’s 2016 introduction and its April 2019 compliance deadline. Forbes México, “Pymes expuestas a multas millonarias por incumplimiento de Código de Red,” January 30, 2020.
  • Secondary reads: Tecsa, “Lo que debes saber para cumplir con el Código de Red 2026,” December 30, 2025; Tecsa, “Sanciones por el incumplimiento del Código de Red para las empresas,” last updated May 21, 2024 (cites the abrogated Ley de la Industria Eléctrica article 165); TLC Magazine México, “Europa comienza a cobrar el impuesto al carbono: exportadores mexicanos enfrentan un nuevo reto comercial,” July 1, 2026.

The MEP newsletter covers CFE tariffs and industrial energy every two weeks, in Spanish.

← Back to Mexico Energy Insights